KUNO ENGELS

Vertriebs-GmbH


KUNO ENGELS Vertriebs-GmbH
Hauptstrasse 42
D-42799 Leichlingen

Phone.: +49 (0)2174 / 7900-0
Fax.: +49 (0)2174 / 7900-10
E-Mail: info@kunoengels.eu

Data Privacy
E-Mail: database@kunoengels.eu

ENGELCANAL® 
ELECTRIC AIR HEATER
Type ELP 1 - ELP 36



Operating voltage:
- precise control

 fig. ELP 16 with STBW 225


pdf
230 VAC
- rapid heating
Circuit: Ph - N
- economical
  - reliable
230 / 400 V three-phase AC
- approved
Circuit: Δ / Y
 
   
Position: universal
profile flange 20 mm

 



 
Type Output



kW
Switch
stages
norm./max

3~ / 1~
Number
of
heating-
grids
 Output per
heating-
grid


kW
B 1



mm
H 1



mm
T



mm
Flange



mm
Duct
galv.
steel

mm
Weight
approx.


kg
ELP 1
1 1/3 3 0.33
250
200
400
20 1.25
7
ELP 1,5
1.5 1/3 3 0.50 250
200
400
20
1.25
7
ELP 3
3
3/9 9 0.33 400
200 500
20
1.25
11.5
ELP 3/6
6 2/6 6 1.00 400
200
500
20
1.25
11.5
ELP 6
6 4/12 12 0.50 500
250
500
20
1.25
15
ELP 9
9
3/9 9
1.00 500
250 500
20
1.25
14
ELP 12
12
4/12 12 1.00 500
250
500
20
1.25
16
ELP 8
8 4/12 12 0.66 500
300
500
20
1.25
15.5
ELP 12-2
12
4/12 12 1.00 500
300 500
20
1.25
16.5
ELP 16
16 4/12 12
1.33 500
300
500
20
1.25
16.5
ELP 10
10 5/15 15
0.66 600
300
500
20
1.25
19
ELP 15
15 5/15 15
1.00 600 300
500
20
1.25
20
ELP 20
20 5/15 15
1.33 600
300
500
20
1.25
21
ELP 15-2
15
5/15 15
1.00 600
350
500
20 1.25
21
ELP 25
25 5/15 15 1.66 600
350
500
20
1.25
22
ELP 30
30 5/15 15
2.00 600
350
500
20
1.25
23
ELP 36 36 6/18 18 2.00 700 400 500 20 1.5 28




































Designed for the market´s needs

    
Safety-tested in compliance with
Low-Voltage Guideline (2006/95/EC)
EMC Guideline (2004/108/EC)
    
Modern and advanced
Developed for air condition technology
      
For heating flowing, dust-free air and non-combustible, non-aggressive and non-explosive gasses up to 333 K (+ 60°C) as standard version.
For all areas, as a pre-heater, after-heater, zone after-heater, duct heater, series unit installation, in standard or optional version (different voltages, dimensions, capacity e.g.).
We offer you an advantageous and user-friendly “storage programme“ as well as solutions made to order.

crucial advantages
- optimal quality at a price suited to output
- delivery ex store
- manufactured in accordance with VDE regulations
- low surface temperature thanks to large-surface
- non-glowing, woven ENGELS-heatinggrid®
- proven in thousands of units
- direct heat transmission via special heat conductors
   located in air flow
- no after-heating
- low air resistance: only approx. 12 Pa at 3 m/s
- available for 100 - 500 V (if necessary up to 690 V)
- superb control by low-time constants
- electric heat exchangers with the greatest heating areas
- multiple output stages
- corrosion-protected, aluminium ducts
- safe and fast electrical connection to terminal strip
- low weight
- universal installation position
- accessories:
   ENGELCONTROL® safety temperature limiter
   ENGELAIR® air flow monitor
   ENGELTHERM® electronic temperature regulator
   ENGELTHERM®-ETDL temperature control units
   ENGELTHYROTEMP TRS temperature control system